Troubleshooting
and Commissioning |
Which tools do you need for troubleshooting and commissioning a running PROFIBUS installation?
There are 2 basic tools which are absolutely necessary! You need a bus analyzer to verify the protocol quality and an oscilloscope to verify the signal quality. With these tools combined you can find 99 % of all errors. ProfiTrace 2 is a Combi-Analyzer that has both tools integrated. The multi-meter is NOT useable for signal analysis! It will only be used to check a connection between 2 points.
 |
What can I do with an oscilloscope?
With the oscilloscope the signal quality of the data communication can be verified. By inspecting the signals al kinds of problems can be identified, like: short-circuits, wire breaks, missing termination, extra termination, EMC and bad electrical interfaces in the devices.
Handling the oscilloscope requires some training, but this will be nothing compared to time and money you safe during troubleshooting and commissioning.
 |
What happens if the PROFIBUS cable has a short-circuit?
A short-circuit in the PROFIBUS cable will in most cases disturb the data communication in the particular segment. The devices in that area will NOT get damaged! The short-circuit can easily be detected with an oscilloscope and even the distance to the problem point. If the end-user wants to keep the installation running during a short-circuit he can pick the following solutions:
• Install a redundant system.
• Divide the installation in more parallel segments coupled by repeaters, OLMs or ProfiHubs.
• Install the cable in secured cable trays.
 |
Why is termination the most common made mistake?
A lot of people are aware that termination has to be powered and placed at both ends cable. What they do not know, is that it has to be placed again when you are using repeaters, OLMs or Profihubs. Every segment has to be terminated. This often slips in when people are using a lot of fibre optic and there is only a short length of copper cable in the cabinets. But even this short cable has to be terminated at both ends.
 |

Installation
and Cabling |
How many PROFIBUS DP repeaters can be placed in series?
In some documentation you will see a maximum of 3 repeaters, even in the standard a reference value of 3 is written, but this is NOT completely true. The internal electronic components of the repeater will determine “the maximum number”. The data regeneration in the repeater will make bits smaller or wider. If you put too many repeaters in series, messages are not recognized anymore, because the bits differentiate too much. Repeaters with no limit are also available. So, check the manual of the repeater! It should state the maximum amount. For example: the Siemens repeater is 9, the ProfiHub is unlimited.
The second step is changing the busparameters. All repeaters have a delay time. If you put a lot of repeaters in series you have to change the Tslot busparameter in the DP master to a higher value. In the manual of the repeater it should state what the value should be.
 |
Why is termination important?
Termination prevents reflections that can disturb the data communication. The higher the baudrate and the longer the cable, the more important termination becomes. Termination should be activated/placed at both ends of every bus segment. With PROFIBUS DP the termination is powered to provide an idle level when nobody is sending data. With PROFIBUS PA the termination is a combination of a resistor and a capacitor.
 |
Should there be distance between PROFIBUS and power cables?
YES, even PROFIBUS can get disturbed by interference caused by parallel high voltage power lines. Always try to have at least 10 cm air space between the cables (depends on the level of the voltage). Most users mix all cables in one cable tray and that often leads to unreliable behaviour. Cables that cross each other will not cause problems. Creating distance is not the only solution. Correct shielding is also a must!
 |
Can you give some basic tips for installing a PROFIBUS DP network?
• Always use PROFIBUS cable and connectors.
• Do not exceed 32 devices per segment (including repeaters, OLMs and couplers).
• Make sure the segment length is in contrast with the baudrate.
• Make sure every segment has powered termination on both ends.
• Avoid spur lines.
• Avoid swapping the wires (A=green, B=red).
• Mark how long the cables really are and update the drawings.
After installation you should test your work:
• Are the addresses correctly set?
• No short circuit or break in the cable?
• Can you communicate with the devices?
 |
Can I put PROFIBUS DP cable in a PA network?
A lot of people think this will never cause a problem because of the high speed signal characteristics, but there are other factors that could make it very unstable:
• There will be too much voltage loss at the end of the cable because of the higher loop resistance of DP cable.
• The cable gets over-powered because of the "thin" 0,64 mm diameter of the DP cable.
Our advise is to only use cable that complies to the PA specifications!
 |
What is the minimum distance between 2 devices on PROFIBUS DP?
When the transmission speed is 1,5 Mbps or higher, it is highly recommended to have at least 1 m of cable between 2 devices. De input capacitance of both devices will be compensated by the cable in order to preserve the common impedance. When the devices would be very close together, there is a big chance the input capacitance causes reflections in the data communication (small short circuits). The effect is much less at transmission speeds lower than 1,5 Mbps.
 |
Does PROFIBUS DP cable always have a violet colour?
NO, because of certain application, protection and isolation classes, PROFIBUS DP cable can have another colour. Example: ground cable and shipboard cable are black, robust cable is green. The standard cable is always violet!
 |
Which pins on the DB9 connector are for communication?
• Pin 3 = B line (red wire)
• Pin 8 = A line (green wire)
The metal casing of the connector is used for the shielding.
 |
What are the advantages of fibre optic against copper wire?
With fibre optic:
• Cable lengths can be longer.
• Complete electrical isolation.
• Elimination of possible ground loops.
But, fibre optic is more expensive than copper (cabling, installation and the required couplers)!
 |
How do you terminate devices that have an M12 connector?
There are 3 ways to terminate devices that have an M12 connector:
- When it has 2 - onboard M12 connectors, put an M12 terminator on the second connector.
- When it has 1 - M12 connector, apply a t-connector that holds the termination and the last connector.
- When the device has onboard termination, switch it on.
 |
PROFIBUS
DP |
Does the PNO update GSD files on their website or CD-ROM?
NO, the manufacturers are responsible to update the GSD files on profibus.com. The PNO does not publish a CD-ROM. The manufacturer website is the best place to download GSD files.
 |
Will the choice of addresses influence the cycle time?
NO, the master will always cyclically communicate with the slaves, so for the cycle time it doesn’t matter what addresses they have.
 |
How many DP slaves can be configured in a network?
Most people say 126, but this is NOT true! The total number of DP slaves that can be put in data-exchange is 124, because of the master that uses an address and the reserved addresses 0 and 126 (these are blocked by the configuration tool). Be careful:
• Address 2 could also be blocked for slaves.
• The master itself can have a limit.
 |
Can I control the outputs of 1 slave with 2 masters (PLCs)?
NO, only 1 PLC has the right to control the outputs (safety feature). The 2nd PLC can only READ the inputs/outputs.
 |
What is the most commonly used transmission speed?
1,5 Mbps is the most commonly used transmission speed. This is the default speed when you create a new project. Most users don’t know what it is and keep this value. Our experience is that most installation are running on a speed that is much too high for the application. When the speed is lower you can have longer cables and less chance of disturbances.
 |
Can I change some settings to make PROFIBUS DP communication more reliable?
YES, in the busparameters of the master you can change some settings to make the communication more reliable:
• Retries/Repeats = 5
• Tqui = 9
• MinTSDR = 22
 |
Is it necessary to reconfigure the bits & bytes in the control system when a new device is added to PROFIBUS?
When a PROFIBUS device is added in the control system configuration, the device gets new memory space assigned, which does NOT conflict with the existing configuration. The existing configuration and program does not need to be touched. This makes PROFIBUS perfect for ‘instrument expansion’ or ‘complete machine copying’.
 |
How is the term “plug and play” used in PROFIBUS?
It has a double meaning; if you replace a device with the same type it works directly, because the configuration is stored in the control system. Also, you can easily integrate a new device in your configuration by importing a GSD file and synchronizing the address of the device. By serving standardized and profile based device descriptions PROFIBUS also enables a manufacturer independent device replacement.
 |
Does PROFIBUS DP have self triggered alarms/diagnostics?
When a device has diagnostics it indicates this during the data exchange. The master will immediately fetch the diagnostics and makes the information available for the end-user. The diagnostics from devices are completely event triggered. Diagnostics are important for smooth and reliable operation. Devices report their own device status and indicate when they need service. This reduces maintenance costs and can increase time between scheduled field visits.
 |

PROFIBUS
PA |
What is FDE (Fault Disconnection Electronics) current?
Some devices consume more power when there is a problem with itself. The FDE current is this additional static/basic current consumption. Some devices have no FDE current. When there is a problem they consume the same current. But when the problem becomes worse, the device shuts itself down from the bus (no more power consumption).
 |
Do simple PA couplers pass through all messages coming from the DP side?
NO, the P+F SK1 coupler does NOT pass the token message (SD4) through.
 |
Can we use EDD and/or DTM on any DP-V1 class 2 master?
NO, each tool uses its own technology:
• PDM: Modified EDD (based on PNO EDD, but not 100% compliant with PNO EDD)
• FieldCare: FDT/DTM technology
• PactWare: FDT/DTM technology
• CommuWin: Executable DLL's (non standard solution)
 |
A PA device has at least 3 function blocks. What are these blocks and what is their purpose?
In the process industry it is common to use blocks to describe the characteristics and functions of a measuring/manipulation point and to represent an application through a combination of these blocks. The specification of PA devices uses this function block model to present functional sequences.
Physical Block (PB)
Describes the necessary parameters and functions of the device itself (e.g. software version, serial number, vendor ID, factory reset command). There is only one Physical block in a PA device.
Transducer Block (TB)
Contains parameters which have effect or describe the type of sensor or actuator. Transducer blocks may also contain parameters for calibration and linearization. The processed information is passed on to the Function Block. If a device has more sensors, it has corresponding Transducer Blocks for every sensor.
Function Block (FB)
Contains one or more cyclically accessible inputs or outputs parameters (process values). These can be of analog or discrete nature. Other parameters: setup scaling, alarms and unit factorization.
 |
What is a Profile within PROFIBUS PA?
Modern PA devices are intelligent and can execute part of the information processing in automation systems. This was previously done by the PLCs or DCS systems. The PA profile is designed with co-operation of the process industry and defines all functions and parameters for different classes of instruments. It is based on internationally accepted function block technology. The profile contains descriptions for the following instrument types:
- Pressure (and differential)
- Level, temperature and flow
- Analog/digital inputs and outputs
- Valves and actuators
- Analyzers
The profile is divided into 2 classes (A and B):
Class A of the profile describes common parameters of simple devices. The scope is limited to the basic functions. This set consists of the process variables (e.g. temperature, pressure, level) added by measured value state, the tag name and the engineering unit.
Class B is an extension to class A and will cover more complex application functions for identification, commissioning, maintenance and diagnosis. The relationship of the parameters to the classes is visible within the parameter definitions and in the conformance statements.
To conclude: The PA profile defines cyclical data + status, diagnostic information and parameters. The PA profile assures “interoperability” and “device exchangeability“
 |
What is a Profile Ident Number?
In cases where the device of manufacturer-A should be replaceable by an equivalent device of manufacturer-B, the standard Ident Number is no longer sufficient because a GSD file is associated with this number. When the device is replaced a change in the configuration is necessary which will lead to a DCS/PLC stop. Therefore the PNO has assigned number ranges to dedicated device types (Profile Ident Numbers) in combination with certain Profile GSD files. A device can support multiple Ident Numbers which are set by a parameterization tool. The end-user has to decide whether to select the Manufacturer specific Ident Number or the Profile Ident Number. Examples:
• Transmitter 0x9700 to 0x970F
• Actuator 0x9710 to 0x971F
• Discrete input 0x9720 to 0x972F
• Discrete output 0x9730 to 0x973F
 |

Product Development and Certification |
For PA certification, does the vendor have to develop its own EDD for the product?
NO, it is not mandatory to have an EDD for PA certification.
 |
For GSD files we can download an editor from profibus.com. Is there an editor for EDD available?
NO, for EDD there is no specific editor. Most engineers just use a plain text editor.
 |
Are all PROFIBUS devices certified?
NO, it is NOT mandatory for a manufacturer to have a PROFIBUS master or slave certified. It is highly recommended, because in most projects only certified devices are selected. At the moment only masters and slaves can be certified. For connectors, cable and repeaters there are no certification guidelines available.
Remark: PROFIsafe and PROFINET devices must be certified.
 |
How do I get a certificate for a tested device?
After receiving a positive test report from the testlab, the manufacturer can apply for a certificate for his device. The form “Application for PROFIBUS Certificate” is used for it. The manufacturer passes the original of the test report together with the form to the PI Certification Office which decides on the certification based on the test report. In case the certification is granted, the manufacturer receives a certificate for the device in question.
 |
I have an HMS ANYBUS card, which is already certified. Do I need to certify my device that holds the card?
The ANYBUS product is part of the entire device and is influenced by a number of criteria like; power supply, EMC, the path from PROFIBUS to the ANYBUS card, GSD file, etc. So certification is still very important!
 |

Others |
What is the cost comparison between conventional and PROFIBUS cabling?
It is a common fact that PROFIBUS reduces cable costs a lot, but there is a more that comes with it:
• Reduction of cable trays.
• Energy savings.
• Less documentation.
• Better overview.
• Reduction of test time.
• Less spare parts.
• Easy to expand or change.
• Shorter downtimes because of quick repair.
• Easy to dismantle.
This is only infrastructure and the initial savings. But the real money making starts with the maintenance and the operational costs. PROFIBUS is an excellent choice, but some training is required to get awareness about the advantages.
 |
What is SINEC L2-DP? Is this different than PROFIBUS DP?
SINEC L2-DP is PROFIBUS DP! Siemens did at one time use their own names for product designation. However, since this proved to be confusing (with L2 in the name), the L2 part of the designation was dropped in favour of just DP to avoid confusion. Another example: SINEC S1 is AS-i.
 |
Is PROFIBUS a single or multi-protocol technology?
Within PROFIBUS there is only one communication layer implemented which is; PROFIBUS DP. Based on this communication layer, several device profiles are defined in the application layer. These profiles provide common data, diagnostics and parameters for the end-user. Sometimes people are confused with PROFIBUS DP and PA, but the only difference is the physical interface. In fact, a PROFIBUS PA device is a PROFIBUS DP device with an application profile suited for the process industry.
 |
Can PROFIBUS meet the requirements for fast communication speed and does it have a longer message length compared to other buses?
PROFIBUS can run on 12 Mbps, which makes it the fastest fieldbus in the world. The messages have only 9 bytes overhead which makes it very efficient. An installation with 30 devices can have a cycle time of less than 1 ms. PROFIBUS is the choice for fast message delivery in the industrial automation environments.
 |
What makes PROFIBUS unique in terms of Cycle time, Real-Time behavior and Diagnostics?
PROFIBUS and PROFINET have the fastest cycle time, which can be less than 1 ms. This cycle time is extremely stable which makes it Real-Time. For diagnostics we have standardized formats and maintenance tools that match perfectly with the demands that maintenance personal has.
 |
What are the benefits of PROFIBUS for the end-users compared to other systems?
First of all PROFIBUS is the only fieldbus that can be used in all parts of the factory (upstream, process and downstream). This means you can use 1 type of control system, 1 knowledge package, 1 group of spare parts and 1 design strategy.
PROFBUS also has a very large number of manufacturers offering products and services. This means for almost every application there is solution and enough backup products available.
These products also have strengths in certain application areas such as; motion control or process control.
PROFIBUS has testlabs that certify products. PROFIBUS guarantees that every product always works with products from other manufacturers.
PROFIBUS has Competence Centers that support the end-users with their automation questions and last but not least, Certified Training Centers provide training.
People from the working groups are working close together to create a better world considering the cost aspect and the environment. They have a special band! Different people from different companies can work together without political, business and personal barriers. All faces pointing to the same direction and we get the job done! The result of their hard work is that; PROFIBUS and PROFINET can save you energy, weight, materials, spare parts, documentation and a lot of effort.
We are a community on which you can rely! Your investment is completely safe for now, the future, yourself and your children.
 |
|