#Profibus_DP GSD_Revision = 2 ; Vendor_Name = "BARTEC GmbH" Model_Name = "Ex I/O BARTEC" ;ORDERNUMBER = "07-7331-2305" Revision = "22.04.1999" Ident_Number = 0x2305 Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release = "HR1" Software_Release = "SR1" ; 9.6_supp = 1 19.2_supp = 1 45.45_supp = 1 93.75_supp = 1 187.5_supp = 1 500_supp = 1 1.5M_supp = 1 ; MaxTsdr_9.6 = 60 MaxTsdr_19.2 = 60 MaxTsdr_45.45 = 250 MaxTsdr_93.75 = 60 MaxTsdr_187.5 = 60 MaxTsdr_500 = 100 MaxTsdr_1.5M = 150 ; Redundancy = 0 Repeater_Ctrl_Sig = 2 24V_Pins = 0 Implementation_Type = "LSPM2" ; Freeze_Mode_supp = 1 Sync_Mode_supp = 1 Auto_Baud_supp = 1 Set_Slave_Add_supp = 0 Min_Slave_Intervall = 1 ; Modular_Station = 0 ;Max_Module = 1 ;Max_Input_Len = 1 ;Max_Output_Len = 1 ;Max_Data_Len = 2 Modul_Offset = 0 User_Prm_Data_Len = 5 User_Prm_Data = 0x00, 0x00, 0x00, 0x00, 0x00 ; Fail_Safe = 0 Slave_Family = 3 Max_Diag_Data_Len = 13 ; Unit_Diag_Bit(16) = "IN ch.1 short circ. / wire break" Unit_Diag_Bit(17) = "IN ch.2 short circ. / wire break" Unit_Diag_Bit(18) = "IN ch.3 short circ. / wire break" Unit_Diag_Bit(19) = "IN ch.4 short circ. / wire break" Unit_Diag_Bit(20) = "IN ch.5 short circ. / wire break" Unit_Diag_Bit(21) = "IN ch.6 short circ. / wire break" Unit_Diag_Bit(22) = "IN ch.7 short circ. / wire break" Unit_Diag_Bit(23) = "IN ch.8 short circ. / wire break" Unit_Diag_Bit(24) = "OUT ch.1 short circ. / overload" Unit_Diag_Bit(25) = "OUT ch.2 short circ. / overload" Unit_Diag_Bit(26) = "OUT ch.3 short circ. / overload" Unit_Diag_Bit(27) = "OUT ch.4 short circ. / overload" Unit_Diag_Bit(28) = "power U2 missing" ; ; Module = "module 1" 0x20,0x10 EndModule ;