ProfiTrace
2 - PROFIBUS Combi-Analyzer on USB |
|
 |

Introduction
ProfiTrace 2 is the most powerful analyzer for PROFIBUS
networks. It is the latest generation in the line of busmonitor
technology because it combines all primary tools in one:
Analyzer, Oscilloscope, Bar
graph, Topology Scan and DP-V0/V1
Master.
Technicians can check and troubleshoot the complete PROFIBUS
network with 1 software package and 1 piece of hardware. This
results in an enormous reduction in equipment, weight, costs
and required knowledge. The advanced USB hardware (ProfiCore
Ultra) is internally equipped with a high-speed digital oscilloscope
and able to capture bus signals running at 12 Mbps.
ProfiTrace is an essential tool for maintenance, commissioning
and troubleshooting as well as product development. Typical
failures such as noise, reflections, voltage drops, termination
problems, double addresses, wire breaks and configuration faults
are easily identified. Random errors such as overshoots, error
telegrams, repeats and diagnostics can also be captured and
logged. The results can also be exported to detailed reports
which are accepted by the industry. Predictive maintenance
and asset management are now really possible! This outstanding
tool that fits in your pocket will boost the capabilities
of service, maintenance and engineering technicians.
 |
Product features |
 |
Analyzer with powerful statistics
Repeats, Fall-outs, Corrupted messages, Diagnostics, Cycle
time, etc. |
 |
High-speed digital oscilloscope
Differential voltage, A-line, B-line, Noise, Overshoots,
Reflections, Triggers. |
 |
Bar graphs
Average, Min. and Max. values of the bus signals per device. |
 |
Topology Scan
Automatic generation of the network topology. |
 |
Reporting
Automatic generation of detailed reports that are accepted
by the industry. |
 |
DP-V0/V1 master
ProfiCaptain has
been completely integrated with even more features. |
 |
ProfiCore Ultra USB interface
Useable on PC platforms, no power supply required and elimination
of spur lines. |
 |
DP and PA
The PA Probe Ultra enables measurements on PA segments. |
 |
9,6 kbps to 12 Mbps. |
 |
Works on XP and Vista platforms. |
 |
Multi language user interface
English, German, Polish.
|
| |
 |
Analyzer features |
Intelligent real-time
Live List
• Colourful representation of detected devices.
• Powerful statistics for every error: repeats, station lost, etc.
• Advice & warnings: Ident number mismatch, Watchdog not set, Illegal configuration.
• Last diagnostic, parameter, configuration and data-exchange message.
• GSD file management for product and diagnostic identification.
Intelligent message sampler
• Visualization of FDL, DP, DP-V1, DP-V2, PA and I&M messages.
• Messages can be filtered and stored.
• Data interpretation of bytes, words, floating points, etc.
• Error detection.
• Bookmarks.
|
 |

[enlarge] -
Dynamic live list with colour status.
[enlarge] -
Message recording with captured retry messages.
 |
ScopeWare features (DP) |

[enlarge] -
Oscilloscope that displays the electrical signals per device.
|
 |
• Time scale: 50 ns to 500 ms.
• Voltage scale: 0,5 to 5 V per DIV.
• Cursor measurement lines (voltage and time).
• Differential (B-A) and single ended (A and/or B line) measurements.
• Trigger per device or free running.
• Trigger features: start of response or request message.
 |
ScopeWare features (PA) |

[enlarge] - Oscilloscope that displays the electrical signals per device.
|
 |
• All features of ScopeWare DP.
• Max. 33 V DC.
• Max. 1,2 Vtt AC.
• AC and DC can be displayed simultaneously.
• Detects missing termination.
• PA Probe Ultra is required.
 |
Bar graph features |

[enlarge] -
Bar graph for the average signal quality.
|
 |
• 2 Selectable modes: Average signal level and minimum difference between 1 and 0.
• Current, Min. and Max. signal level indicator per device.
• Colours state the quality of the signals.
• Continuously updated.
 |
Topology Scan |
• Automatic generation of the network topology.
• No shutdown required!
• No disturbance in the cycle time!
• Works on 500 kbps and 1,5 Mbps.
• On passive networks in conjunction with ProfiCaptain.
|
 |

[enlarge] -
Automatic generation of the network topology.
 |
Reporting |
• Generation of detailed network reports.
• Address list with manufacturer information.
• Oscilloscope images of every device.
• Live List, Bar graph and Topology structure.
• Summary of detected errors.
• Standard layout for signatures and approvals.
• Import of company logo.
Click here for a report example.
 |
 |

[enlarge] -
Generation of detailed network reports.
 |
Master features |
• Complete integration of ProfiCaptain.
• Putting slaves in Data Exchange.
• I/O testing with automatic patterns.
• Automatic detection of existing busparameters.
• Brand new concept of 'stealing' slaves.
• Class 2 functions in a Class 1 framework.
• No shutdowns when updating the configuration.
• Deactivating slaves in the configuration.
 |
 |

[enlarge] -
Master for I/O testing and network diagnostics.
 |
ProfiCore
Ultra features |
PROFIBUS
• PROFIBUS baudrate max. 12 Mbps.
• Galvanic isolated PROFIBUS interface.
• Latest RS 485 technology.
Oscilloscope
• Frequency: 2 x 192 MHz.
• Bandwidth: 100 MHz.
• Differential measurement: -9 to +9 V.
• Single ended: -4,5 to +8 V.
Others
• High-speed USB 2.0 interface.
• External power supply possible if required.
 |
Remarks |
Downloads & Links |
|
Copyright ©2009 PROCENTEC. All rights reserved.
- info@procentec.com -
+31-(0)174-671800 - Update:
29 June, 2009
 |
 |